陶瓷企业煤气站雷电灾害风险评估
陶瓷企业煤气站雷电灾害风险评估
摘要:陶瓷企业煤气站属于易燃易爆场所,依据中国气象局第20号令《防雷减灾管理办法》,必须对其进行雷电灾害风险评估。本文阐述了恩平市景瑜陶瓷有限公司煤气站的雷电灾害风险评估过程,分别就人身伤亡损失风险和经济损失风险进行估算并得出结论,说明了怎样对陶瓷企业煤气站进行雷电灾害风险评估。
关键词:煤气站,雷电灾害,风险评估,人身伤亡损失,经济损失
Abstract: the ceramic enterprises belongs to the gas station in flammable and explosive place, according to the China meteorological administration order 20 the lightning protection and management method “, we must carry on the lightning disaster risk assessment. This paper expounds the EnPingShi JingYu ceramics Co., LTD. Of the gas station lightning disaster risk assessment process, personal injury respectively loss risk and economic loss risk estimate and concluded, and explains how to ceramic enterprise gas station for lightning disaster risk assessment.
Keywords: gas station, lightning, risk assessment, person casualties loss, economic loss
引言
自2007年开始,恩平市陆续引进新建了多家陶瓷企业,每个陶瓷企业厂区都达到数万平方米。厂区建有煤气站、窑炉车间、抛光车间、球磨车间、喷雾塔、办公楼、宿舍楼等等。这些陶瓷企业都是恩平市内的大型建设工程,煤气站更属于易燃易爆场所,因此,做好陶瓷企业厂区的雷电灾害风险评估工作是我们义不容辞的责任。因评估建筑物太多,本文仅以恩平市景瑜陶瓷有限公司煤气站为例,说明陶瓷企业煤气站的雷电灾害风险评估。
1 相关数据采集
1.1煤气站工程概况
恩平市景瑜陶瓷有限公司位于沙湖镇蒲桥工业区,厂区场地为山丘地带。总平面布置如图1:该煤气站总用地面积3028.5m2 ,设有煤气站房(内安装有5台煤气发生炉)、机房、电房、储气柜、煤气输送管道等。煤气站房长45m ,宽12.5m ,高28.4m ,人员大多在煤气站房内操作;电房长35m ,宽14m ,高6.5m ;周围有其他车间、厂房等,高度都未超过煤气站房的高度。供电线缆采用埋地屏蔽电缆,长约22m. ,线缆间有变压器;场地全部为混凝土硬化,地面下无绝缘