一起110kV电容式电压互感器介损异常的原因分析
一起110kV电容式电压互感器介损异常的原因分析
摘要:本文介绍了厦门电业局在例行试验中发现一例110kV电容式电压互感器电容量、油试验正常,但介损超标的异常现象,经对互感器开展诊断性试验,结合解体检查情况,判断该互感器电容芯子存在先天不足,深层绝缘干燥不彻底,随着运行时间的加长,内层绝缘的潮气逐渐扩散到外层,使得介损超标。
关键词:电容式电压互感器;介损
Abstract: The paper introduces one abnormal 110kV capacitor voltage transformer (CVT) was found by a routine test in Xiamen Power Supply Bureau. The Capacitance and oil of CVT is qualified, but dielectric loss is over-standard. After diagnostic test and disassembling inspection, congenitally deficient of Capacitor was found. The Capacitor’s deep layer insulation was not completely dry, With the running time of growth, internal insulation moisture gradually spread to the outer layer, the dielectric loss exceeding standard.
Key words: Capacitor Voltage Transformer (CVT); dielectric loss
0前言
电容式电压互感器(CVT)是由高压电容分压器和电磁单元组成的一种电压变换装置,具有绝缘监测方便、维护简单、运行可靠、价格便宜等优点,在电力系统得到了广泛的应用。但是由于受到设计、工艺及原材料等影响,存在较多质量问题,威胁到电网安全稳定运行。厦门电业局在一次例行性试验,发现了110kV电容式电压互感器电容量、油试验正常,但介损超标的异常现象,经过解体分析,判断出该互感器的电容芯出厂前由于工艺管控的影响,深层绝缘干燥不彻底,导致设备运行一段时间后介损超标。
1 故障情况
2012年10月16日,工作人员在例行性试验时,发现某110kV电压互感器 B相(设备型号:TYD110/√3-0.01W3,2011年8月1日出厂,2011年09月27日投运)的分压电容C2介质损耗为0.293%(具体数值见表1),超过了《输变电设备状态检修试验规程》规定的注意值0.25%,且较交接试验的数据发生了明显变化,初步判断该设备绝缘存在缺陷。为了查明原因,2012年10月30日,对该台设备进行试验并解体检查。
表1 110kV电压互感器的试验数据
试 验 性 质 交接试验 例行性试验
试 验 日 期 2011-09-18 2012-10-16